Description
- Be safer: Measure voltage to 1000 V ac through the open fork, without test leads.
- Be faster: No need to open covers or remove wire nuts.
- Be more efficient: Simultaneously measure voltage and current.
- Be everywhere: 17.8 mm open fork is widest in the industry; measure up to 200 A on 4/0 wires (120 mm2).
- Go beyond simple detection. Actually measure ac voltage and current values without test leads.
| Measurement Specifications | ||||
|---|---|---|---|---|
| Function | Requires test leads | Range | Resolution | Accuracy[1] |
| FieldSense ac voltage true-rms | No | 1000 V | 1 V | ± (3 % + 3 counts) 45 Hz – 66 Hz[2][3] |
| FieldSense ac current true-rms | No | 200.0 A | 0.1 A | ± (3% + 3 counts) 45 Hz – 66 Hz |
| FieldSense frequency (Hz) | No | 45 Hz – 66 Hz | 1 Hz | ± (1% + 2 counts)[3] |
| Volts ac true-rms | Yes | 1000 V | 1 V | ± (1.5% + 2 counts) 45 Hz – 66 Hz |
| Volts dc | Yes | 1000 V | 1 V | ± (1% + 2 counts) |
| Resistance | Yes | 2000 Ω | 1 Ω | ± (1% + 2 counts) |
| Yes | 20.00 kΩ | 0.01 kΩ | ||
| Yes | 100.0 kΩ | 0.1 kΩ | ||
| Safety | 1000 V CAT III 600 V CAT IV | |||
Specifications
- Calibration: 1-year calibration cycle
- Jaw opening: 17.8mm
| Temperature | Operating | -10 °C to +50 °C (14 °F to 122 °F) |
| Storage | -30 °C to +60 °C (-22 °F to +140 °F) | |
| Altitude | Operating | 2,000 m (6,562 feet) |
| Storage | 10,000 m (32,808 feet) | |
| Relative Humidity | 0% to 90%, 5 °C to 30 °C (41 °F to 86 °F) | |
| 0% to 75%, 30°C to 40 °C (86 °F to 104 °F) | ||
| 0% to 45%, 40°C to 50 °C (104 °F to 122 °F) | ||
| Battery Type and Life | 2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense | |
| Temperature coefficient | 0.1 x (specified accuracy) / °C for <18°C or >28 °C | |
| 0.1 x (specified accuracy) / °C for <18°C or >28 °C | ||
| Safety | IEC/EN 61010-1: Pollution Degree 2 | |
| Electromagnetic Environment | IEC/EN 61326-1: Portable | |









Reviews